40.5kV Solid Insulated Switchgear
This shield solid insulated switchgear can be applied to a power supply system of rated voltage of 35kV, AC 50Hz and terminal power supply. Its specification can comply with the provisions of IEC298 with application of power grid, factory distribution, high voltage transmission, railway system, urban power distribution, wind power generations.
Product Advantages
Solid Insulation
Shielded layer of conductive material makes the surface at earth potential everywhere; it is accidently touchable providing safety features for operator.This shielded solid insulated switchgear, which is completely solid insulated, has entire circuit insulated by epoxy and silicon rubber, leaves no live parts in free air; givenless affection of dirt, humidity and pollutions etc.; requires less necessity for maintenance. Each phase is selfcontained into single epoxy block, significantly reducing phadischarge and risks of internal arc fault.
Modular architecture
Modular architecture enables reduction of switchgear dimensionsDimensions of Solid Insulated Switchgear: 700 × 2000 × 1150 it is only 1/6 of traditional air insulated type ie KYN61.
Optimized Electric Field
Computing technology facilitate optimal design of electric field and isolation.
Safety
Sealed electrified body IP67.
Inner cone cable terminal to improve the connection reliability.
Extreme Environment Application
Suitable for cold, high altitude, humidity, corrosion, lowland and explosion-proof area.
All Operating Condition Environment
- Ambient temperature: -50°C ~ +70°C;
- Altitude: ≤ 5500 m
- Internal and external arcing test report (switches, bus bar, cable compartment) detection
- Immersion detection test report
- Salt spray testing report
- The circuit breaker is composed of mechanism transmission box and circuit breaker poles.
Parameters
Parameter Title | Unit | Vacuum Circuit Breaker | Disconnecting Switch | Earthing Switch |
---|---|---|---|---|
Rated Voltage | kV | 40.5 | 40.5 | 40.5 |
Arc Quenching | - | Vacuum | - | - |
Rated Current | A | 1250 | 1250 | 1250 |
Rated Frequency | Hz | 50/60 | 50/60 | 50/60 |
Main Circuit Resistance | μΩ | ≤120 | ≤120 | ≤120 |
Power Frequency Withstand Voltage(1 min) | kV | 118 | 118 | 118 |
Lightning Impulse Withstand Voltage | kV | 215 | 215 | 215 |
Rated Short-circuit Breaking Current | kA | 31.5 | - | - |
Breaking Times | times | 30 | - | - |
Rated Short-circuit Making Current | kA | 80 | - | - |
Rated Short-time Withstand Current/ Duration | kA/S | 31.5/4s | 31.5/4s | 31.5/4s |
Rated Peak Withstand Current | kA | 80 | 80 | 80 |
Internal Arcing Test (AFLR level) | kA/S | 31.5kA/0.5s (including bus compartment, switch compartment, cable compartment) | ||
Degree of Protection | - | IP67 | IP67 | IP67 |
Mechanical Endurance | Times | 10000 | 3000 | 3000 |